Microfiche records prior to 2006 have not been completely digitized and may not be available yet on PRO. If you cannot find what you are looking for please submit a records request.

PRO is currently experiencing an outage. Some documents and records may not be available on PRO momentarily. We apologize for the inconvenience and are working to restore full access.

Permit Number: T06CM03011
Parcel: 132130570

Review Status: Completed

Review Details: POST 3RD PARTY REVIEW

Permit Number - T06CM03011
Review Name: POST 3RD PARTY REVIEW
Review Status: Completed
Review Date Reviewer's Name Type of Review Description Status Comments
10/30/2006 DAVE MANN FIRE REVIEW Denied Basement must have sprinklers per IFC 903.2.10.1.

Please add the following automatic sprinkler criteria to the plans:

1. The hazard classification of the occupancy including any special hazards.
2. The design standard to be used.
3. The availability and adequacy of the water supply.
4. The design density and the area of operation.
10/31/2006 STEVE SHIELDS ZONING REVIEW Approved
10/31/2006 BETSY COTTLE COMMERCIAL IMPACT FEE COMMERCIAL IMPACT FEE PROCESSING Completed impact fees do apply - no development or site plan approved within deadline
western district
15200 sf $15546.40
11/07/2006 JASON GREEN ENGINEERING REVIEW Approved

Final Status

Task End Date Reviewer's Name Type of Review Description
11/14/2006 DELMA ROBEY OUT TO CUSTOMER Completed
11/14/2006 DELMA ROBEY REJECT SHELF Completed