Permit Number: T06CM02968
Parcel: 113071710

Review Status: Completed

Review Details: RESUBMITTAL

Permit Number - T06CM02968
Review Name: RESUBMITTAL
Review Status: Completed
Review Date Reviewer's Name Type of Review Description Status Comments
10/10/2006 WILDAN 2ND PARTY REVIEW REVIEW Denied October 10, 2006

City of Tucson
201 North Stone Avenue
Tucson, AZ 85711

RE: LOVEJOY RESIDENCE – 2nd REVIEW
CITY OF TUCSON LOG NO. T06CM02968
WILLDAN PROJECT NO. 13881-6027

The initial review for the above project has been completed. This letter contains comments which need to be addressed by written responses to each which indicate any actions taken. In order to facilitate a shorter second review, all corrections and revisions must be made on the original plans and two complete new sets of prints, along with one complete redlined set, must be returned to our office. To avoid delays, ensure that all corrections have been made, are complete, and have been coordinated on all applicable detail and note sheets, and that all changes have been highlighted with appropriate revision numbers, revision dates, and “cloud bubbles.” Pen or pencil corrections on final prints are not acceptable.

This project has been reviewed for conformance with the 2003 IRC, 1997 UAC, 2003 IMC, 2003 IECC, 2002 NEC codes with local modifications, and the 2003 UPC with State of Arizona Amendments. Any revisions to this plan will require an additional review and approval by Willdan.

Should you have questions regarding the comments herein, please contact your plans examiner Antonio Moya.

Occupancy Occup. Load Construction Area S.F. Sprinklered Alarms
SFR
Porch N/A V-B 2888
240 No Smoke

Special Inspection is required for the following items:
N/A

The following items are acceptable for deferred submittals:
N/A

ARCHITECTURAL COMMENTS:
Sheet S3
On Detail 11, please provide the GA or UL listing for the fire-rated wall. Reference 2003 IRC Section R317. COMMENT REMAINS: Listing given cannot be found in the 2003 IBC. Please reference all codes to the current City of Tucson adopted codes.

STRUCTURAL COMMENTS:
Reviewed and accepted.

PLUMBING COMMENTS:
Sheet P1
Waterline: Provide the total fixture unit demand (based on Tables 6-4 & 7-3 or Tables L-1 & L-2) and the maximum developed length. Reference UPC Section 610. COMMENT REMAINS: Not addressed.

The fire-rated wall shall not have any penetrations. Please provide rerouting to avoid any penetrations. Reference 2003 IRC R317. COMMENT REMAINS: Please provide a special inspection certificate for all rated caulking and UL approved fire stops. Please provide that it will comply with ASTME 814 or UL 1479 and fire-resistance-rated assembly. Reference 2003 IRC Sections R317.3.1.2 and R317.3.1.1.

MECHANICAL COMMENTS:
Reviewed and accepted.

ELECTRICAL COMMENTS:
Sheet E1
Where ceiling fans are shown on the plans, provide a note indicating only approved outlet boxes shall be used. Reference IRC Section E4001.6. COMMENT REMAINS: Please revise Note # 8 to the current 2003 IRC.

Please provide cut sheets for all the exterior light fixtures shown. The cut sheets need to provide lumens per fixture, and show if the fixture is a full cut-off, which means no light is emitted at or above the horizontal plane. Please provide calculations for all exterior lighting fixtures. Reference the City of Tucson Outdoor Lighting Code. COMMENT REMAINS: The lamp options information is missing. Please provide clear cut sheets. Reference IRC Section 106.1.1 and the City of Tucson Outdoor Lighting Code.

Cross-reference exterior lighting fixtures on the plans with the cut sheets and calculations submitted. Reference the City of Tucson Submittal Requirements. COMMENT REMAINS: Not addressed.

ENERGY CODE COMMENTS:
Reviewed and accepted.

ACCESSIBILITY COMMENTS:
Reviewed and accepted.

Sincerely,

WILLDAN




Martin Haeberle, C.B.O.
Building Official

MAH/tb