Review Date Reviewer's Name Type of Review Description Status Comments
06/15/2006 BETH GRANT COMMERCIAL IMPACT FEE COMMERCIAL IMPACT FEE PROCESSING Passed
06/16/2006 ROBERT SHERRY PLUMBING-COMMERCIAL REVIEW Denied 1. Provide information to show that the size of the existing water meter conforms to the sizing guidelines of Tucson Water. Reference Section 610.1, UPC 2003.
2. Provide clearance between the water heater and the electrical panel per Table 110.26 A1, NEC 2002.
3. Complete the waste and vent isometrics to include all of the relocated fixtures. Show the new location of the flow control for the grease trap. Reference Section 103.2.3, UPC 2003.
4. Provide backflow protection for all appliances to be directly connected to the water supply system that do not have listed, integral backflow preventers or integral air gaps. Reference Section 603.0, UPC 2003.
06/16/2006 ROBERT SHERRY WATER REVIEW Approved
06/16/2006 ROBERT SHERRY MECHANICAL-COMMERCIAL REVIEW Denied Provide information to show that the make up air for the kitchen hood complies with Section 508.1.1, IMC 2003.
06/29/2006 GERRY KOZIOL WWM REVIEW Approved
07/21/2006 GBONILL1 BUILDING-COMMERCIAL REVIEW Needs Review