Permit Number: T06CM02885
Parcel: 136061540

Review Status: Completed

Review Details: COMMERCIAL TI

Permit Number - T06CM02885
Review Name: COMMERCIAL TI
Review Status: Completed
Review Date Reviewer's Name Type of Review Description Status Comments
05/25/2006 LINDA BUCZYNSKI ELECTRICAL-COMMERCIAL REVIEW Denied T06CM02885 5/25/06

1. IECC allows 0.9 W/SF, not 1.69, for restaurant tenant areas. The figure used is for the whole building.
2. Receptacle load appears to be 1080 VA, not 7320; this is Circuit 29. Kitchen loads at 65% appear to be 11161 VA, not 11,086; this was circuits 3, 7-18, 20, 22, 24, 31. Fixed loads appear to be 10096 VA, not 650; ckts 1,5, 19, 21, 23, 25, 27, 34. Remaining mechanical loads appear to be 5236, not 4976, considering ckts 33-35, 36-38, and 40-42. Load total appears to be 50723 VA, not 47182. Current draw appears to be 140.9A, not 130.9.
06/15/2006 GBONILL1 WWM REVIEW Needs Review
06/15/2006 GBONILL1 PLUMBING-COMMERCIAL REVIEW Needs Review
06/15/2006 GBONILL1 WATER REVIEW Needs Review
06/15/2006 GBONILL1 BUILDING-COMMERCIAL REVIEW Needs Review
06/15/2006 GBONILL1 MECHANICAL-COMMERCIAL REVIEW Needs Review