Review Date | Reviewer's Name | Type of Review | Description | Status | Comments |
---|---|---|---|---|---|
05/16/2006 | HEATHER THRALL | ZONING | REVIEW | Approved | |
05/16/2006 | ANY | ENGINEERING | REVIEW | Approved | |
05/16/2006 | LINDA BUCZYNSKI | ELECTRICAL-COMMERCIAL | REVIEW | Denied | T06CM02885 5/16/06 1. Rework IECC compliance. This is a restaurant, not an office. Reference Table 805.5.2. 2. Put panel and circuit # on WP 30/2 disconnect on north side of kitchen. 3. Plans Examiner calculates panel to be 142A, not 130.9. Please revisit these calcs to give the Owner a better sense of spare capacity. 4. According to Line Diagram, Panel A is 100A. According to Panel Schedule it is 200A. Please clarify. |
05/16/2006 | DAVE MANN | FIRE | REVIEW | Approved | |
05/25/2006 | AOLIVO1 | MECHANICAL-COMMERCIAL | REVIEW | Needs Review | |
05/25/2006 | AOLIVO1 | PLUMBING-COMMERCIAL | REVIEW | Needs Review | |
05/25/2006 | AOLIVO1 | WATER | REVIEW | Needs Review | |
05/25/2006 | AOLIVO1 | BUILDING-COMMERCIAL | REVIEW | Needs Review | |
05/25/2006 | AOLIVO1 | WWM | REVIEW | Needs Review |