Permit Number: T06CM02885
Parcel: 136061540

Review Status: Completed

Review Details: COMMERCIAL TI

Permit Number - T06CM02885
Review Name: COMMERCIAL TI
Review Status: Completed
Review Date Reviewer's Name Type of Review Description Status Comments
05/16/2006 HEATHER THRALL ZONING REVIEW Approved
05/16/2006 ANY ENGINEERING REVIEW Approved
05/16/2006 LINDA BUCZYNSKI ELECTRICAL-COMMERCIAL REVIEW Denied T06CM02885 5/16/06

1. Rework IECC compliance. This is a restaurant, not an office. Reference Table 805.5.2.
2. Put panel and circuit # on WP 30/2 disconnect on north side of kitchen.
3. Plans Examiner calculates panel to be 142A, not 130.9. Please revisit these calcs to give the Owner a better sense of spare capacity.
4. According to Line Diagram, Panel A is 100A. According to Panel Schedule it is 200A. Please clarify.
05/16/2006 DAVE MANN FIRE REVIEW Approved
05/25/2006 AOLIVO1 MECHANICAL-COMMERCIAL REVIEW Needs Review
05/25/2006 AOLIVO1 PLUMBING-COMMERCIAL REVIEW Needs Review
05/25/2006 AOLIVO1 WATER REVIEW Needs Review
05/25/2006 AOLIVO1 BUILDING-COMMERCIAL REVIEW Needs Review
05/25/2006 AOLIVO1 WWM REVIEW Needs Review