Microfiche records prior to 2006 have not been completely digitized and may not be available yet on PRO. If you cannot find what you are looking for please submit a records request.

Permit Number: T06CM02884
Parcel: 12701003W

Review Status: Completed

Review Details: RESUBMITTAL

Permit Number - T06CM02884
Review Name: RESUBMITTAL
Review Status: Completed
Review Date Reviewer's Name Type of Review Description Status Comments
05/23/2006 ROBERT SHERRY MECHANICAL-COMMERCIAL REVIEW Approved
05/23/2006 ROBERT SHERRY PLUMBING-COMMERCIAL REVIEW Denied Based on the supplied data for the water supply (45 PSI, 160 feet) and using Table 6-5, 2003 UPC, the piping is undersized.