Review Details: COMMERCIAL TI

Permit Number - T06CM02884
Review Name: COMMERCIAL TI
Review Status: Completed
Review Date Reviewer's Name Type of Review Description Status Comments
05/16/2006 HEATHER THRALL ZONING REVIEW Approved
05/16/2006 ROBERT SHERRY MECHANICAL-COMMERCIAL REVIEW Denied Provide information on the sequence of operation for the restroom exhaust to show that recirculation of the air from the restroom will not occur. Reference Section 403.2.1, IMC 2003.
05/16/2006 LINDA BUCZYNSKI ELECTRICAL-COMMERCIAL REVIEW Approved
05/16/2006 ROBERT SHERRY WATER REVIEW Approved
05/16/2006 RAUL PALMA BUILDING-COMMERCIAL REVIEW Approved
05/16/2006 ANY ENGINEERING REVIEW Approved
05/16/2006 ROBERT SHERRY PLUMBING-COMMERCIAL REVIEW Denied 1. Show how the temperature of the hot water supply to the public lavatories is controlled. Reference Section 414.1, UPC 2003 and Section 804.3, IECC 2003.
2. Show how the new water piping relates to the existing water supply system and show that the additional connections do not cause the existing piping to be overloaded. Reference Section 101.5.1, UPC 2003.
05/16/2006 DAVE MANN FIRE REVIEW Approved
05/23/2006 GERRY KOZIOL WWM REVIEW Approved