Permit Review Detail
Review Status: Completed
Review Details: COMMERCIAL TI
Permit Number - T06CM02883
Review Name: COMMERCIAL TI
Review Status: Completed
| Review Date | Reviewer's Name | Type of Review | Description | Status | Comments |
|---|---|---|---|---|---|
| 05/16/2006 | HEATHER THRALL | ZONING | REVIEW | Approved | |
| 05/16/2006 | ROBERT SHERRY | MECHANICAL-COMMERCIAL | REVIEW | Approved | |
| 05/16/2006 | LINDA BUCZYNSKI | ELECTRICAL-COMMERCIAL | REVIEW | Approved | T06CM02883 5/16/06 1. For the feeder calculation, a minimum of 75 VA per linear foot shall be counted for the lighting tracks. If they are reasonable expected to operate for 3 hours or more, a 25% demand factor shall be used for continuous load. 2. It is not clear from the panel calculations they lighting/continuous load/largest motor DF of 25% has been taken. Please clarify. |
| 05/16/2006 | ROBERT SHERRY | WATER | REVIEW | Approved | |
| 05/16/2006 | RAUL PALMA | BUILDING-COMMERCIAL | REVIEW | Approved | |
| 05/16/2006 | RSHERRY1 | WWM | REVIEW | Passed | |
| 05/16/2006 | ROBERT SHERRY | PLUMBING-COMMERCIAL | REVIEW | Passed | |
| 05/16/2006 | JASON GREEN | ENGINEERING | REVIEW | Approved | |
| 05/16/2006 | DAVE MANN | FIRE | REVIEW | Approved |