Permit Number: T06CM02869
Parcel: 13104405A

Address:
4917 E 29TH ST

Review Status: Completed

Review Details: REVISION - - 1ST

Permit Number - T06CM02869
Review Name: REVISION - - 1ST
Review Status: Completed
Review Date Reviewer's Name Type of Review Description Status Comments
08/21/2006 ROBERT SHERRY PLUMBING-COMMERCIAL REVIEW Denied 1. Provide a copy of the approved plumbing drawing for this project as reference.
2. The submitted riser diagram shows a cross connection between potable water and the drain system and an undersized condensate drain from an A/C system.
3. Show how the hot water temperature at the lavatory is to be maintained at 110 degrees or less.
4. Provide a cleanout for the relocated lavatory.