Permit Review Detail
Review Status: Completed
Review Details: REVISION - - 1ST
Permit Number - T06CM02869
Review Name: REVISION - - 1ST
Review Status: Completed
Review Date | Reviewer's Name | Type of Review | Description | Status | Comments |
---|---|---|---|---|---|
08/21/2006 | ROBERT SHERRY | PLUMBING-COMMERCIAL | REVIEW | Denied | 1. Provide a copy of the approved plumbing drawing for this project as reference. 2. The submitted riser diagram shows a cross connection between potable water and the drain system and an undersized condensate drain from an A/C system. 3. Show how the hot water temperature at the lavatory is to be maintained at 110 degrees or less. 4. Provide a cleanout for the relocated lavatory. |
Final Status
Task End Date | Reviewer's Name | Type of Review | Description |
---|---|---|---|
08/23/2006 | CINDY AGUILAR | APPROVAL SHELF | Completed |
08/23/2006 | CINDY AGUILAR | OUT TO CUSTOMER | Completed |