Permit Number: T06CM02869
Parcel: 13104405A

Address:
4917 E 29TH ST

Review Status: Completed

Review Details: COMMERCIAL TI

Permit Number - T06CM02869
Review Name: COMMERCIAL TI
Review Status: Completed
Review Date Reviewer's Name Type of Review Description Status Comments
05/15/2006 HEATHER THRALL ZONING REVIEW Approved
05/15/2006 ROBERT SHERRY MECHANICAL-COMMERCIAL REVIEW Denied Show that the restroom ventilation complies with the requirements of Section 403.3, IMC 2003.
05/15/2006 ROBERT SHERRY PLUMBING-COMMERCIAL REVIEW Approved
05/15/2006 ROBERT SHERRY WATER REVIEW Approved
05/15/2006 DOUG LAAKSO BUILDING-COMMERCIAL REVIEW Denied S1. PROVIDE OFFICIAL ADDRESS SLIP FOR COMBINATION OF TWO SUITES, 4917 AND 4919 E 29th ST.
S2. PROVIDE DETAILS FOR NEW OPENINGS, INCLUDING WIDTH AND HEIGHT AND SHOW BEARING OR NON-BEARING CONDITIONS.
S3. CLARIFY VALUATION.
05/15/2006 MARTIN BROWN FIRE REVIEW Approved
05/18/2006 GERRY KOZIOL WWM REVIEW Approved
05/18/2006 AKLAPPE1 ELECTRICAL-COMMERCIAL REVIEW Needs Review
05/18/2006 AKLAPPE1 ENGINEERING REVIEW Needs Review