Permit Review Detail
Review Status: Completed
Review Details: COMMERCIAL TI
Permit Number - T06CM02869
Review Name: COMMERCIAL TI
Review Status: Completed
| Review Date | Reviewer's Name | Type of Review | Description | Status | Comments |
|---|---|---|---|---|---|
| 05/15/2006 | HEATHER THRALL | ZONING | REVIEW | Approved | |
| 05/15/2006 | ROBERT SHERRY | MECHANICAL-COMMERCIAL | REVIEW | Denied | Show that the restroom ventilation complies with the requirements of Section 403.3, IMC 2003. |
| 05/15/2006 | ROBERT SHERRY | PLUMBING-COMMERCIAL | REVIEW | Approved | |
| 05/15/2006 | ROBERT SHERRY | WATER | REVIEW | Approved | |
| 05/15/2006 | DOUG LAAKSO | BUILDING-COMMERCIAL | REVIEW | Denied | S1. PROVIDE OFFICIAL ADDRESS SLIP FOR COMBINATION OF TWO SUITES, 4917 AND 4919 E 29th ST. S2. PROVIDE DETAILS FOR NEW OPENINGS, INCLUDING WIDTH AND HEIGHT AND SHOW BEARING OR NON-BEARING CONDITIONS. S3. CLARIFY VALUATION. |
| 05/15/2006 | MARTIN BROWN | FIRE | REVIEW | Approved | |
| 05/18/2006 | GERRY KOZIOL | WWM | REVIEW | Approved | |
| 05/18/2006 | AKLAPPE1 | ELECTRICAL-COMMERCIAL | REVIEW | Needs Review | |
| 05/18/2006 | AKLAPPE1 | ENGINEERING | REVIEW | Needs Review |