Permit Number: T06CM02867
Parcel: 127010090

Review Status: Completed

Review Details: COMMERCIAL TI

Permit Number - T06CM02867
Review Name: COMMERCIAL TI
Review Status: Completed
Review Date Reviewer's Name Type of Review Description Status Comments
05/18/2006 ROBERT SHERRY PLUMBING-COMMERCIAL REVIEW Approved
05/18/2006 ROBERT SHERRY MECHANICAL-COMMERCIAL REVIEW Denied Show that the roof structure is able to support HP-4.
05/22/2006 LINDA BUCZYNSKI ELECTRICAL-COMMERCIAL REVIEW Approved T06CM02867 5/18/06

1. New HVAC is 33.5 A protected by a 60A CB on Electrical. This unit is specified by Mechanical as 25.6 MCA 30 MOCP.
2. Show window receptacles shall be counted at 200 VA per LF, for the Feeder calculation. Reference NEC 220.12 (A). This effects Ckts R-9, S-15, and T-18.
06/07/2006 GERRY KOZIOL WWM REVIEW Approved
06/07/2006 CHRISTY FOREMAN BUILDING-COMMERCIAL REVIEW Approved