Permit Review Detail
Review Status: Completed
Review Details: COMMERCIAL TI
Permit Number - T06CM02867
Review Name: COMMERCIAL TI
Review Status: Completed
| Review Date | Reviewer's Name | Type of Review | Description | Status | Comments |
|---|---|---|---|---|---|
| 05/18/2006 | ROBERT SHERRY | MECHANICAL-COMMERCIAL | REVIEW | Denied | Show that the roof structure is able to support HP-4. |
| 05/18/2006 | ROBERT SHERRY | PLUMBING-COMMERCIAL | REVIEW | Approved | |
| 05/22/2006 | LINDA BUCZYNSKI | ELECTRICAL-COMMERCIAL | REVIEW | Approved | T06CM02867 5/18/06 1. New HVAC is 33.5 A protected by a 60A CB on Electrical. This unit is specified by Mechanical as 25.6 MCA 30 MOCP. 2. Show window receptacles shall be counted at 200 VA per LF, for the Feeder calculation. Reference NEC 220.12 (A). This effects Ckts R-9, S-15, and T-18. |
| 06/07/2006 | CHRISTY FOREMAN | BUILDING-COMMERCIAL | REVIEW | Approved | |
| 06/07/2006 | GERRY KOZIOL | WWM | REVIEW | Approved |