Review Details: COMMERCIAL TI

Permit Number - T06CM02867
Review Name: COMMERCIAL TI
Review Status: Completed
Review Date Reviewer's Name Type of Review Description Status Comments
05/15/2006 HEATHER THRALL ZONING REVIEW Approved
05/15/2006 ROBERT SHERRY MECHANICAL-COMMERCIAL REVIEW Denied 1. Clarify the termination of the condensate drain for HP-4; there is no lav in the area shown.
2. Revise the outside air calculation for HP-3 per Equation 4-1, Section 403.3.2, IMC 2003.
3. Show how recirculation of the air from the restrooms is to be prevented. Reference Section 403.2, IMC 2003.
4. Show that the roof structure is able to support HP-4.
05/15/2006 ROBERT SHERRY PLUMBING-COMMERCIAL REVIEW Denied 1. Show how the water heater is the be adequately blocked and anchored to the wall.
2. The minimum insulation for recirculating hot water systems is 1". Reference Section 804.5, IECC 2003.
05/15/2006 ROBERT SHERRY WATER REVIEW Approved
05/15/2006 MARTIN BROWN FIRE REVIEW Approved
05/15/2006 SUZANNE BOHNET ENGINEERING REVIEW Approved
05/18/2006 LINDA BUCZYNSKI ELECTRICAL-COMMERCIAL REVIEW Needs Review INCOMPLETE O/C REVIEW. OK TO SUBMIT OR TRY AGAIN TOMORROW MORNING. SHEET E1.02 NEEDS REVIEW.

T06CM02867 5/18/06

1. New HVAC is protected by a 60A CB on electrical, but the Mechanical Schedule calls for MOCP 30. It appears that Electrical is considering this as a larger unit than does Mechanical.

3. Show windows shall be counted at 200 VA per LF. Reference NEC 220.12 (A). Ckts R-9, T-15B and S-15.
05/18/2006 GBONILL1 WWM REVIEW Needs Review
05/18/2006 GBONILL1 BUILDING-COMMERCIAL REVIEW Needs Review