Permit Review Detail
Review Status: Completed
Review Details: RESUBMITTAL
Permit Number - T06CM02734
Review Name: RESUBMITTAL
Review Status: Completed
| Review Date | Reviewer's Name | Type of Review | Description | Status | Comments |
|---|---|---|---|---|---|
| 08/29/2006 | ROBERT SHERRY | PLUMBING-COMMERCIAL | REVIEW | Denied | The backflow prevention device (Wilkins model 700), specified to be used in the supply to the pet fountain to prevent a cross-connection with the other bubblers, is not recognized as a double check valve backflow prevention assembly by the UPC because it is not testable. See Table 6-2, UPC 2003 for use in this situation (Contamination with back-siphonage). Reference Sections 310.4 and 603.2.4, UPC 2003 |
| 09/06/2006 | CHRISTY FOREMAN | BUILDING-COMMERCIAL | REVIEW | Approv-Cond | DEFERRED SUBMITTAL FOR STRUCURAL CALCULATIONS FOR 3 ENTRY CANOPIES |
| 09/20/2006 | MARTY DUPONT | ADA | REVIEW | Approved |
Final Status
| Task End Date | Reviewer's Name | Type of Review | Description |
|---|---|---|---|
| 09/21/2006 | JMORALE1 | OUT TO CUSTOMER | Completed |
| 09/21/2006 | SUE REEVES | REJECT SHELF | Completed |