Microfiche records prior to 2006 have not been completely digitized and may not be available yet on PRO. If you cannot find what you are looking for please submit a records request.

Permit Number: T06CM02734
Parcel: Unknown

Address:
905 S CONCERT PL

Review Status: Completed

Review Details: RESUBMITTAL

Permit Number - T06CM02734
Review Name: RESUBMITTAL
Review Status: Completed
Review Date Reviewer's Name Type of Review Description Status Comments
08/29/2006 ROBERT SHERRY PLUMBING-COMMERCIAL REVIEW Denied The backflow prevention device (Wilkins model 700), specified to be used in the supply to the pet fountain to prevent a cross-connection with the other bubblers, is not recognized as a double check valve backflow prevention assembly by the UPC because it is not testable. See Table 6-2, UPC 2003 for use in this situation (Contamination with back-siphonage). Reference Sections 310.4 and 603.2.4, UPC 2003
09/06/2006 CHRISTY FOREMAN BUILDING-COMMERCIAL REVIEW Approv-Cond DEFERRED SUBMITTAL FOR STRUCURAL CALCULATIONS FOR 3 ENTRY CANOPIES
09/20/2006 MARTY DUPONT ADA REVIEW Approved

Final Status

Task End Date Reviewer's Name Type of Review Description
09/21/2006 JMORALE1 OUT TO CUSTOMER Completed
09/21/2006 SUE REEVES REJECT SHELF Completed