Permit Number: T06CM02734
Parcel: Unknown

Address:
905 S CONCERT PL

Review Status: Completed

Review Details: COMMERCIAL TI

Permit Number - T06CM02734
Review Name: COMMERCIAL TI
Review Status: Completed
Review Date Reviewer's Name Type of Review Description Status Comments
06/20/2006 DAVE MANN FIRE REVIEW Approved
06/21/2006 ROBERT SHERRY MECHANICAL-COMMERCIAL REVIEW Passed
06/21/2006 ROBERT SHERRY PLUMBING-COMMERCIAL REVIEW Denied 1. Specify the backflow prevention device to be used in the supply to the pet fountain to prevent a cross-connection with the other bubblers. Reference Sections 310.4 and 603.0, UPC 2003
2. Clarify how backflow protection is being provided for the quick-coupling valves that appear to be connected to the potable water system. Reference Section 603.4.7, UPC 2003.
06/21/2006 ROBERT SHERRY WATER REVIEW Approved
06/27/2006 LINDA BUCZYNSKI ELECTRICAL-COMMERCIAL REVIEW Approved
06/28/2006 GERRY KOZIOL WWM REVIEW Passed
07/12/2006 PATRICIA GILBERT ENGINEERING REVIEW Approved
07/17/2006 BETH GRANT COMMERCIAL IMPACT FEE COMMERCIAL IMPACT FEE PROCESSING Passed
07/18/2006 CHRISTY FOREMAN BUILDING-COMMERCIAL REVIEW Denied STRUCTURAL REVIEW COMMENTS

DATE: 7/19/06
ACTIVITY NUMBER: T06CM02734
PROJECT NAME: Off-leash dog area
PROJECT ADDRESS: 905 S. Concert Pl.
ARCHITECT / ENGINEER: John R. Hucko
PROJECT REVIEWER: Christy Foreman



TRANSMIT ORIGINAL DRAWINGS WITH NEXT SUBMITTAL.

PLEASE CALL AT 791-5550 X1108 OR EMAIL AT CFOREMA1@CI.TUCSON.AZ.US IF YOU CARE TO DISCUSS.

1)Provide structural calculations and shop drawings for covered entries.
2)Clarify attachment of veneer on masonry piers.
3) Provide detail 2/E-0 for light pole base per requirements in structural calculation.
4)Provide detail per structural calculations for detail 6/L-9.
5) Dimension lineal feet of 6ft steel tube fence with pilasters.
6) Clarify slope on accessible path.
07/27/2006 MARTY DUPONT ADA REVIEW Denied This project has been reviewed by the City of Tucson Office of Equal Opportunity Programs for compliance with the Department of Justice 28 CFR Part 36 ADA Standards for Accessible Design.

1) Provide the running & cross slopes for all new concrete walks. Running slopes shall not exceed 5% and the cross slope shall not exceed 2% ยง4.3.7
08/10/2006 TERRY STEVENS ZONING REVIEW Approved

Final Status

Task End Date Reviewer's Name Type of Review Description
08/15/2006 DELMA ROBEY OUT TO CUSTOMER Completed
08/15/2006 SUE REEVES REJECT SHELF Completed