Review Status: Completed
Review Details: COMMERCIAL TI
Permit Number - T06CM02700
Review Name: COMMERCIAL TI
Review Status: Completed
| Review Date | Reviewer's Name | Type of Review | Description | Status | Comments |
|---|---|---|---|---|---|
| 05/08/2006 | HEATHER THRALL | ZONING | REVIEW | Approved | |
| 05/08/2006 | JASON GREEN | ENGINEERING | REVIEW | Approved | |
| 05/09/2006 | LINDA BUCZYNSKI | ELECTRICAL-COMMERCIAL | REVIEW | Needs Review | |
| 05/09/2006 | ROBERT SHERRY | MECHANICAL-COMMERCIAL | REVIEW | Approved | |
| 05/09/2006 | CHRISTY FOREMAN | BUILDING-COMMERCIAL | REVIEW | Denied | 1)BEFORE THIS PERMIT CAN BE ISSUED PERMIT #T00PL00865 NEEDS TO BE FINALED. THIS PERMIT IS EXPIRED. 2) PROVIDE EXIT SIGNAGE. 3) 1 HR. EXIT CORRIDOR IS REQUIRED FOR BACK EXIT SEE TABLE 1016.1. 4) TEXT HEIGHT ON DRAWINGS SHALL BE A MINIMUM OF 1/8". |
| 05/09/2006 | ROBERT SHERRY | WATER | REVIEW | Approved | |
| 05/09/2006 | ROBERT SHERRY | PLUMBING-COMMERCIAL | REVIEW | Denied | 1. Provide information to show that the new HW & CW piping will not overload a portion of the existing piping. 2. What is a "swoop T"? |
| 05/15/2006 | MARTIN BROWN | FIRE | REVIEW | Denied | Cannot exit thru storage. |
| 05/16/2006 | CAGUILA1 | WWM | REVIEW | Needs Review |