Permit Number: T06CM02700
Parcel: 12702231F

Review Status: Completed

Review Details: COMMERCIAL TI

Permit Number - T06CM02700
Review Name: COMMERCIAL TI
Review Status: Completed
Review Date Reviewer's Name Type of Review Description Status Comments
05/08/2006 HEATHER THRALL ZONING REVIEW Approved
05/08/2006 JASON GREEN ENGINEERING REVIEW Approved
05/09/2006 LINDA BUCZYNSKI ELECTRICAL-COMMERCIAL REVIEW Needs Review
05/09/2006 ROBERT SHERRY MECHANICAL-COMMERCIAL REVIEW Approved
05/09/2006 CHRISTY FOREMAN BUILDING-COMMERCIAL REVIEW Denied 1)BEFORE THIS PERMIT CAN BE ISSUED PERMIT #T00PL00865 NEEDS TO BE FINALED. THIS PERMIT IS EXPIRED.
2) PROVIDE EXIT SIGNAGE.
3) 1 HR. EXIT CORRIDOR IS REQUIRED FOR BACK EXIT SEE TABLE 1016.1.
4) TEXT HEIGHT ON DRAWINGS SHALL BE A MINIMUM OF 1/8".
05/09/2006 ROBERT SHERRY WATER REVIEW Approved
05/09/2006 ROBERT SHERRY PLUMBING-COMMERCIAL REVIEW Denied 1. Provide information to show that the new HW & CW piping will not overload a portion of the existing piping.
2. What is a "swoop T"?
05/15/2006 MARTIN BROWN FIRE REVIEW Denied Cannot exit thru storage.
05/16/2006 CAGUILA1 WWM REVIEW Needs Review