Permit Review Detail
Review Status: Completed
Review Details: COMMERCIAL TI
Permit Number - T06CM02695
Review Name: COMMERCIAL TI
Review Status: Completed
| Review Date | Reviewer's Name | Type of Review | Description | Status | Comments |
|---|---|---|---|---|---|
| 05/08/2006 | TERRY STEVENS | ZONING | REVIEW | Approved | |
| 05/08/2006 | ANY | ENGINEERING | REVIEW | Approved | |
| 05/10/2006 | LINDA BUCZYNSKI | ELECTRICAL-COMMERCIAL | REVIEW | Needs Review | |
| 05/10/2006 | ROBERT SHERRY | MECHANICAL-COMMERCIAL | REVIEW | Denied | 1.Show the route and termination point of the condensate drain. Termination over the roof is not allowed. 2. The minimum font size for all drawings is 1/8", all upper case. 3. Specify the minimum resistance (R-value) of the duct insulation to be used on this project. Reference Section 803.2.8, IECC 2003. |
| 05/10/2006 | RAUL PALMA | BUILDING-COMMERCIAL | REVIEW | Denied | 1) Provide detail 20/A8.1. |
| 05/10/2006 | ROBERT SHERRY | WATER | REVIEW | Approved | |
| 05/10/2006 | ROBERT SHERRY | PLUMBING-COMMERCIAL | REVIEW | Denied | 1. The minimum font size for all drawings is 1/8", all upper case. 2. Show all of the loads connected to the gas meter along with the developed length of the existing piping. 3. The tubs shall be directly connected to the sanitary waste system. 4. Show that the additional water piping does not overload the existing water distribution piping. |
| 05/10/2006 | MARTIN BROWN | FIRE | REVIEW | Approved | |
| 05/11/2006 | GBONILL1 | WWM | REVIEW | Needs Review |