Permit Number: T06CM02695
Parcel: 12708187F

Review Status: Completed

Review Details: COMMERCIAL TI

Permit Number - T06CM02695
Review Name: COMMERCIAL TI
Review Status: Completed
Review Date Reviewer's Name Type of Review Description Status Comments
05/08/2006 TERRY STEVENS ZONING REVIEW Approved
05/08/2006 ANY ENGINEERING REVIEW Approved
05/10/2006 LINDA BUCZYNSKI ELECTRICAL-COMMERCIAL REVIEW Needs Review
05/10/2006 ROBERT SHERRY MECHANICAL-COMMERCIAL REVIEW Denied 1.Show the route and termination point of the condensate drain. Termination over the roof is not allowed.
2. The minimum font size for all drawings is 1/8", all upper case.
3. Specify the minimum resistance (R-value) of the duct insulation to be used on this project. Reference Section 803.2.8, IECC 2003.
05/10/2006 RAUL PALMA BUILDING-COMMERCIAL REVIEW Denied 1) Provide detail 20/A8.1.
05/10/2006 ROBERT SHERRY WATER REVIEW Approved
05/10/2006 ROBERT SHERRY PLUMBING-COMMERCIAL REVIEW Denied 1. The minimum font size for all drawings is 1/8", all upper case.
2. Show all of the loads connected to the gas meter along with the developed length of the existing piping.
3. The tubs shall be directly connected to the sanitary waste system.
4. Show that the additional water piping does not overload the existing water distribution piping.
05/10/2006 MARTIN BROWN FIRE REVIEW Approved
05/11/2006 GBONILL1 WWM REVIEW Needs Review