Permit Number: T06CM02688
Parcel: 14121024M

Review Status: Completed

Review Details: COMMERCIAL TI

Permit Number - T06CM02688
Review Name: COMMERCIAL TI
Review Status: Completed
Review Date Reviewer's Name Type of Review Description Status Comments
06/20/2006 ROBERT SHERRY MECHANICAL-COMMERCIAL REVIEW Approved
06/21/2006 RAUL PALMA BUILDING-COMMERCIAL REVIEW Approved
06/21/2006 LINDA BUCZYNSKI ELECTRICAL-COMMERCIAL REVIEW Denied TRANSMIT ORIGINAL DRAWINGS WITH NEXT SUBMITTAL.

PLEASE CALL AT 791-5550 X1106 OR EMAIL AT Linda.Buczynski@tucsonaz.gov
IF YOU CARE TO DISCUSS.

1. Panel B high phase carries 171A. A 100A bus is indicated on the panel schedule. Please clarify.
2. Mechanical Plans specify a new 240V, 2-HP 3-phase EF. No such new equipment on electrical plans, and no source of 240V shown on plans.
3. Electrical plans are titled "Existing Conditions to be Permitted." Sheet A0.1 General Plan Note 2 refers to "electrical, power, lighting, HVAC, and accessories" as existing conditions which need permitting. Please show all such items as new on this plan set, and provide the usual specifications.
07/07/2006 BETH GRANT COMMERCIAL IMPACT FEE COMMERCIAL IMPACT FEE PROCESSING Passed