Review Details: COMMERCIAL TI

Permit Number - T06CM02688
Review Name: COMMERCIAL TI
Review Status: Completed
Review Date Reviewer's Name Type of Review Description Status Comments
05/31/2006 LINDA BUCZYNSKI ELECTRICAL-COMMERCIAL REVIEW Denied TRANSMIT ORIGINAL DRAWINGS WITH NEXT SUBMITTAL.

PLEASE CALL AT 791-5550 X1106 OR EMAIL AT Linda.Buczynski@tucsonaz.gov
IF YOU CARE TO DISCUSS.

1. Provide circuit and/or panel information for the electrical load(s).
2. Specify conduit and conductor size and type.
3. Provide feeder/service load calculations.
4. Registered Electrical Engineer shall identify perimeter of classified location on plans. Note that it is the policy of the City that if a paint spray booth is not listed, the entire building is to be classified.
5. Plot the location of any electrical equipment installed in classified location. Provide specifications for this equipment. Specifications shall comply with NEC Article 501 and 516 requirements.
05/31/2006 ROBERT SHERRY MECHANICAL-COMMERCIAL REVIEW Denied Show how the design of the exhaust termination complies with Section 502.7.3.6 (1), IMC 2003.
06/20/2006 AKLAPPE1 BUILDING-COMMERCIAL REVIEW Needs Review
06/20/2006 AKLAPPE1 WWM REVIEW Needs Review