Review Status: Completed
Review Details: COMMERCIAL TI
Permit Number - T06CM02688
Review Name: COMMERCIAL TI
Review Status: Completed
| Review Date | Reviewer's Name | Type of Review | Description | Status | Comments |
|---|---|---|---|---|---|
| 05/31/2006 | LINDA BUCZYNSKI | ELECTRICAL-COMMERCIAL | REVIEW | Denied | TRANSMIT ORIGINAL DRAWINGS WITH NEXT SUBMITTAL. PLEASE CALL AT 791-5550 X1106 OR EMAIL AT Linda.Buczynski@tucsonaz.gov IF YOU CARE TO DISCUSS. 1. Provide circuit and/or panel information for the electrical load(s). 2. Specify conduit and conductor size and type. 3. Provide feeder/service load calculations. 4. Registered Electrical Engineer shall identify perimeter of classified location on plans. Note that it is the policy of the City that if a paint spray booth is not listed, the entire building is to be classified. 5. Plot the location of any electrical equipment installed in classified location. Provide specifications for this equipment. Specifications shall comply with NEC Article 501 and 516 requirements. |
| 05/31/2006 | ROBERT SHERRY | MECHANICAL-COMMERCIAL | REVIEW | Denied | Show how the design of the exhaust termination complies with Section 502.7.3.6 (1), IMC 2003. |
| 06/20/2006 | AKLAPPE1 | BUILDING-COMMERCIAL | REVIEW | Needs Review | |
| 06/20/2006 | AKLAPPE1 | WWM | REVIEW | Needs Review |