Review Status: Completed
Review Details: COMMERCIAL TI
Permit Number - T06CM02688
Review Name: COMMERCIAL TI
Review Status: Completed
| Review Date | Reviewer's Name | Type of Review | Description | Status | Comments |
|---|---|---|---|---|---|
| 05/08/2006 | HEATHER THRALL | ZONING | REVIEW | Approved | |
| 05/08/2006 | ROBERT SHERRY | MECHANICAL-COMMERCIAL | REVIEW | Denied | 1. Provide information regarding the material being exhausted and the quantities being used or stored. 2. Provide the dimensions of the booth face area. 3. Provide flow data for the overspray filters. 4. Provide manufacturer's data (e.g. Cut sheets) for the exhaust fan. 5. Show how the exhaust fan is being supported. 6. Provide listing information for the proposed backdraft damper that shows it is suitable for this application. |
| 05/08/2006 | JWILLIA5 | ELECTRICAL-COMMERCIAL | REVIEW | Needs Review | |
| 05/08/2006 | ROBERT SHERRY | WATER | REVIEW | Approved | |
| 05/08/2006 | RAUL PALMA | BUILDING-COMMERCIAL | REVIEW | Denied | 1) WHAT DO ITEMS I AND 2 REFER TO? 2) PROVIDE CONNECTION OF METAL PANEL TO WALL. |
| 05/08/2006 | JASON GREEN | ENGINEERING | REVIEW | Approved | |
| 05/08/2006 | ROBERT SHERRY | PLUMBING-COMMERCIAL | REVIEW | Passed | |
| 05/08/2006 | MARTIN BROWN | FIRE | REVIEW | Approved | |
| 05/31/2006 | JMORALE1 | WWM | REVIEW | Needs Review |