Permit Number: T06CM02688
Parcel: 14121024M

Review Status: Completed

Review Details: COMMERCIAL TI

Permit Number - T06CM02688
Review Name: COMMERCIAL TI
Review Status: Completed
Review Date Reviewer's Name Type of Review Description Status Comments
05/08/2006 HEATHER THRALL ZONING REVIEW Approved
05/08/2006 ROBERT SHERRY MECHANICAL-COMMERCIAL REVIEW Denied 1. Provide information regarding the material being exhausted and the quantities being used or stored.
2. Provide the dimensions of the booth face area.
3. Provide flow data for the overspray filters.
4. Provide manufacturer's data (e.g. Cut sheets) for the exhaust fan.
5. Show how the exhaust fan is being supported.
6. Provide listing information for the proposed backdraft damper that shows it is suitable for this application.
05/08/2006 JWILLIA5 ELECTRICAL-COMMERCIAL REVIEW Needs Review
05/08/2006 ROBERT SHERRY WATER REVIEW Approved
05/08/2006 RAUL PALMA BUILDING-COMMERCIAL REVIEW Denied 1) WHAT DO ITEMS I AND 2 REFER TO?
2) PROVIDE CONNECTION OF METAL PANEL TO WALL.
05/08/2006 JASON GREEN ENGINEERING REVIEW Approved
05/08/2006 ROBERT SHERRY PLUMBING-COMMERCIAL REVIEW Passed
05/08/2006 MARTIN BROWN FIRE REVIEW Approved
05/31/2006 JMORALE1 WWM REVIEW Needs Review