Permit Number: T06CM02686
Parcel: 14041127D

Review Status: Completed

Review Details: RESUBMITTAL - SITE

Permit Number - T06CM02686
Review Name: RESUBMITTAL - SITE
Review Status: Completed
Review Date Reviewer's Name Type of Review Description Status Comments
07/24/2006 PETER MCLAUGHLIN ZONING REVIEW Denied Upon completion of the following revision, an over the counter review may be arranged to obtain stamped approval by the zoning review section without resubmitting the site plan. The following item must be revised on or added to the site plan:

In the LUC Summary, revise the MS&R street perimeter yard building setback (east) from Alvernon Way to state that it is required to be the greater of 21 feet or the height of the exterior building wall (38 feet) measured from the back of future curb location rather than 1/2 the building height as stated. Remove reference to "1/2 building height".
LUC 3.2.6.5
LUC 3.2.6.5
07/24/2006 ANDREW CONNOR LANDSCAPE REVIEW Approved
07/24/2006 PETER MCLAUGHLIN ZONING HC SITE REVIEW Approved
08/08/2006 JASON GREEN ENGINEERING REVIEW Approved DATE: August 9, 2006
SUBJECT: Fire Station #22
TO: Michael Becherer, WSM Architects
LOCATION: 6810 S Alvernon Way, T15S R14E Sec16, Ward 5
REVIEWERS: Jason Green, CFM
ACTIVITY: T06CM02686


SUMMARY: Engineering Division of Development Services Department has received and reviewed the re-submitted site plan, landscape plan, drainage report and the submitted geotechnical report. The drainage report was reviewed for site plan purpose only. Engineering Division recommends approval of the site plan with the following condition:

1. Provide a typical sand/oil interceptor at the drainpipe for the hose wash out area. The wash out area must provide for a sand/oil interceptor prior to the runoff entering the sewer system.



For any questions call me at 791-5550, extension 1189.


Jason Green, CFM
Senior Engineer Associate
Engineering Division
Development Services
08/14/2006 MARTY DUPONT ADA REVIEW Approved

Final Status

Task End Date Reviewer's Name Type of Review Description
08/17/2006 CINDY AGUILAR OUT TO CUSTOMER Completed
08/17/2006 SUE REEVES REJECT SHELF Completed