Permit Number: T06CM02590
Parcel: 140420200

Review Status: Completed

Review Details: OTHER

Permit Number - T06CM02590
Review Name: OTHER
Review Status: Completed
Review Date Reviewer's Name Type of Review Description Status Comments
07/03/2006 LINDA BUCZYNSKI ELECTRICAL-COMMERCIAL REVIEW Approved T06CM02590 6/20/06

1. Add to Note #1 on single line diagram: "Service #2 on east wall. Service #3 on exterior west wall."
2. Add to Note #2 on single line diagram: "Service #1 on south wall. Service #3 on exterior west wall."
3. Add to Note #3 on single line diagram: "Services #2 and #3 in Electrical Room. Door to electrical room on north wall."
4. Change the #1 CU Grounding Electrode conductor to 2/0. Reference NEC Table 250.66.
5. Battery charger is 3-phase according to circuit designation on Sheet E-2 and breaker designation on panel schedule. Yet it's load is only listed on 2 phases. Please clarify.