Permit Review Detail
Review Status: Completed
Review Details: OTHER
Permit Number - T06CM02590
Review Name: OTHER
Review Status: Completed
Review Date | Reviewer's Name | Type of Review | Description | Status | Comments |
---|---|---|---|---|---|
07/03/2006 | LINDA BUCZYNSKI | ELECTRICAL-COMMERCIAL | REVIEW | Approved | T06CM02590 6/20/06 1. Add to Note #1 on single line diagram: "Service #2 on east wall. Service #3 on exterior west wall." 2. Add to Note #2 on single line diagram: "Service #1 on south wall. Service #3 on exterior west wall." 3. Add to Note #3 on single line diagram: "Services #2 and #3 in Electrical Room. Door to electrical room on north wall." 4. Change the #1 CU Grounding Electrode conductor to 2/0. Reference NEC Table 250.66. 5. Battery charger is 3-phase according to circuit designation on Sheet E-2 and breaker designation on panel schedule. Yet it's load is only listed on 2 phases. Please clarify. |