Permit Number: T06CM02590
Parcel: 140420200

Review Status: Completed

Review Details: COMMERCIAL TI

Permit Number - T06CM02590
Review Name: COMMERCIAL TI
Review Status: Completed
Review Date Reviewer's Name Type of Review Description Status Comments
05/02/2006 CHRISTY FOREMAN BUILDING-COMMERCIAL REVIEW Passed
05/02/2006 ROBERT SHERRY MECHANICAL-COMMERCIAL REVIEW Passed
05/02/2006 ROBERT SHERRY PLUMBING-COMMERCIAL REVIEW Passed
05/02/2006 ROBERT SHERRY WATER REVIEW Approved
05/02/2006 RSHERRY1 WWM REVIEW Passed
05/03/2006 HEATHER THRALL ZONING REVIEW Approved
05/03/2006 JASON GREEN ENGINEERING REVIEW Approved
05/04/2006 LINDA BUCZYNSKI ELECTRICAL-COMMERCIAL REVIEW Denied T06CM02590 5/3/06

1. Show location of Battery Charger on plans.
2. Specify conduit and conductor size and type for any circuit exceeding 20A.
3. Clarify intent with respect to service. Line diagram indicates two existing services, one at 208V and another at 480V; new disconnects come off of new gutter powered by existing raceway; 5 disconnect switches total. Sheet E-2 shows the existing 480V service interior and does not clarify the exact location of the 208V existing service; it appears that the new disconnects to the existing service are exterior, and if the existing disconnects are interior then they are not grouped per NEC 230.72 (A). Keynote 2 implies a new additional service.
05/04/2006 MARTIN BROWN FIRE REVIEW Approved