Permit Review Detail
Review Status: Completed
Review Details: COMMERCIAL TI
Permit Number - T06CM02590
Review Name: COMMERCIAL TI
Review Status: Completed
Review Date | Reviewer's Name | Type of Review | Description | Status | Comments |
---|---|---|---|---|---|
05/02/2006 | CHRISTY FOREMAN | BUILDING-COMMERCIAL | REVIEW | Passed | |
05/02/2006 | ROBERT SHERRY | MECHANICAL-COMMERCIAL | REVIEW | Passed | |
05/02/2006 | ROBERT SHERRY | PLUMBING-COMMERCIAL | REVIEW | Passed | |
05/02/2006 | ROBERT SHERRY | WATER | REVIEW | Approved | |
05/02/2006 | RSHERRY1 | WWM | REVIEW | Passed | |
05/03/2006 | HEATHER THRALL | ZONING | REVIEW | Approved | |
05/03/2006 | JASON GREEN | ENGINEERING | REVIEW | Approved | |
05/04/2006 | LINDA BUCZYNSKI | ELECTRICAL-COMMERCIAL | REVIEW | Denied | T06CM02590 5/3/06 1. Show location of Battery Charger on plans. 2. Specify conduit and conductor size and type for any circuit exceeding 20A. 3. Clarify intent with respect to service. Line diagram indicates two existing services, one at 208V and another at 480V; new disconnects come off of new gutter powered by existing raceway; 5 disconnect switches total. Sheet E-2 shows the existing 480V service interior and does not clarify the exact location of the 208V existing service; it appears that the new disconnects to the existing service are exterior, and if the existing disconnects are interior then they are not grouped per NEC 230.72 (A). Keynote 2 implies a new additional service. |
05/04/2006 | MARTIN BROWN | FIRE | REVIEW | Approved |