Permit Number: T06CM02577
Parcel: 11627504B

Review Status: Completed

Review Details: RESUBMITTAL

Permit Number - T06CM02577
Review Name: RESUBMITTAL
Review Status: Completed
Review Date Reviewer's Name Type of Review Description Status Comments
07/06/2006 LINDA BUCZYNSKI ELECTRICAL-COMMERCIAL REVIEW Denied TRANSMIT ORIGINAL DRAWINGS WITH NEXT SUBMITTAL.

PLEASE CALL AT 791-5550 X1106 OR EMAIL AT Linda.Buczynski@tucsonaz.gov
IF YOU CARE TO DISCUSS.

1. Provide the schedule on the plans for the floodlights, as required by the Tucson Lighting Code, Section 8.1 Submittal Contents, 8.1.6, http://www.tucsonaz.gov/dsd/Codes___Ordinances/Tucson_Lighting_Code.pdf.
2. UNRESPONSIVE. Sheet E4 Detail 2, please specify the backfill material.
3. UNRESPONSIVE. Electrical design not complete. Missing FROM THE PLANS are such items as lighting fixture schedule, generator, panel schedule, equipment locations, circuit designations, specification of conduit and conductor size and type.
07/11/2006 RAUL PALMA BUILDING-COMMERCIAL REVIEW Approved

Final Status

Task End Date Reviewer's Name Type of Review Description
08/02/2006 GERARDO BONILLA OUT TO CUSTOMER Completed
08/02/2006 SUE REEVES REJECT SHELF Completed