Microfiche records prior to 2006 have not been completely digitized and may not be available yet on PRO. If you cannot find what you are looking for please submit a records request.

Permit Number: T06CM02577
Parcel: 11627504B

Review Status: Completed

Review Details: CELL TOWER/ANTENNAS

Permit Number - T06CM02577
Review Name: CELL TOWER/ANTENNAS
Review Status: Completed
Review Date Reviewer's Name Type of Review Description Status Comments
05/02/2006 MARTIN BROWN FIRE REVIEW Approved
05/10/2006 LINDA BUCZYNSKI ELECTRICAL-COMMERCIAL REVIEW Denied TRANSMIT ORIGINAL DRAWINGS WITH NEXT SUBMITTAL.

PLEASE CALL AT 791-5550 X1106 OR EMAIL AT Linda.Buczynski@tucsonaz.gov
IF YOU CARE TO DISCUSS.

1. There appear to be floodlights by the door of the proposed structure. Please note that any addition to lighting at this site shall be tallied in compliance with the Tucson Lighting Code, http://www.tucsonaz.gov/dsd/Codes___Ordinances/Tucson_Lighting_Code.pdf.
2. Minimum font size is 1/8".
3. Sheet E1 Specification 3.08 please provide color coding according to the City of Tucson Amendments to the NEC, http://www.tucsonaz.gov/dsd/2002_NEC_amend.pdf.
4. Sheet E1 Specification 3.06, there is no NEC 250-81 (C). Please provide references from the 2002 Code.
5. Sheet E4 Detail 2, please specify the warning tape per NEC 300.5 (D) (3).
6. Sheet E4 Detail 2, please specify the backfill material.
7. Provide available fault current at service, and fault current rating of equipment.
8. Electrical design not complete. Missing such items as generator, panel schedule, equipment locations, circuit designations, specification of conduit and conductor size and type.
05/24/2006 CRAIG GROSS ZONING REVIEW Approved
05/24/2006 DAN CASTRO PLANNING-CITY HALL REVIEW Approved
05/24/2006 JAY HOGAN COMMUNICATIONS REVIEW Approved
05/30/2006 JASON GREEN ENGINEERING REVIEW Approved DATE: May 30, 2006
SUBJECT: 3645 W Starr Pass Bl- 6 Panel Antennas
TO: Randy Pridgeon/ Cortel LLC
LOCATION: T14S R13E Sec17, Ward 1
REVIEWERS: Jason Green, CFM
ACTIVITY: T06CM02577


SUMMARY: Engineering Division of Development Services Department has received and reviewed the submitted site plan (T06CM02577) for the above referenced property. Engineering recommends approval of the site plan with the following condition added to the permit:

ยท Contractor is to provide positive drainage away from structure.

There is no resubmittal required. Pick up permits after approvals from all review entities have been completed. If you have any questions, I can be reached at 791-5550, extension 1189.



Jason Green, CFM
Senior Engineer Associate
Engineering Division
Development Services
06/06/2006 RAUL PALMA BUILDING-COMMERCIAL REVIEW Denied 1) Sheet S-4 detail 1, specify the length of the 3/8" dia.
lag screw.
2) The max. passive pressure per section 1804.2.1 is
250 pcf. Calcs show 275.

Final Status

Task End Date Reviewer's Name Type of Review Description
06/08/2006 GBONILL1 OUT TO CUSTOMER Completed
06/08/2006 SUE REEVES REJECT SHELF Completed