Permit Review Detail
Review Status: Completed
Review Details: RESUBMITTAL
Permit Number - T06CM02576
Review Name: RESUBMITTAL
Review Status: Completed
| Review Date | Reviewer's Name | Type of Review | Description | Status | Comments |
|---|---|---|---|---|---|
| 03/01/2007 | ROBERT SHERRY | PLUMBING-COMMERCIAL | REVIEW | Denied | 1. Third request. Provide information (I.E. PROVIDE INFORMATION FROM THE MANUFACTURER OF THE GREASE INTERCEPTOR) to show that the specified interceptor complies with the provisions of Appendix H, UPC 2003. See Section H 105.0, Construction Requirements. Note: the referenced cover, the Neenah R-1792 is not gasketed, as is required by Section H 105.2.3, UPC 2003. |
Final Status
| Task End Date | Reviewer's Name | Type of Review | Description |
|---|---|---|---|
| 03/09/2007 | FSANCHE1 | OUT TO CUSTOMER | Completed |
| 03/09/2007 | SUE REEVES | REJECT SHELF | Completed |