Review Date Reviewer's Name Type of Review Description Status Comments
03/01/2007 ROBERT SHERRY PLUMBING-COMMERCIAL REVIEW Denied 1. Third request. Provide information (I.E. PROVIDE INFORMATION FROM THE MANUFACTURER OF THE GREASE INTERCEPTOR) to show that the specified interceptor complies with the provisions of Appendix H, UPC 2003. See Section H 105.0, Construction Requirements. Note: the referenced cover, the Neenah R-1792 is not gasketed, as is required by Section H 105.2.3, UPC 2003.

Final Status

Task End Date Reviewer's Name Type of Review Description
03/09/2007 FSANCHE1 OUT TO CUSTOMER Completed
03/09/2007 SUE REEVES REJECT SHELF Completed