Microfiche records prior to 2006 have not been completely digitized and may not be available yet on PRO. If you cannot find what you are looking for please submit a records request.

Permit Number: T06CM02576
Parcel: 14118001H

Review Status: Completed

Review Details: RESUBMITTAL

Permit Number - T06CM02576
Review Name: RESUBMITTAL
Review Status: Completed
Review Date Reviewer's Name Type of Review Description Status Comments
02/15/2007 ROBERT SHERRY PLUMBING-COMMERCIAL REVIEW Denied Second request. Provide information to show that the specified interceptor complies with the provisions of Appendix H, UPC 2003. See Section H 105.0, Construction Requirements. Note: the referenced cover, the Neenah R-1792 is not gasketed, as is required by Section H 105.2.3, UPC 2003.
02/21/2007 LEERAY HANLY BUILDING-COMMERCIAL REVIEW Approved

Final Status

Task End Date Reviewer's Name Type of Review Description
02/26/2007 FSANCHE1 OUT TO CUSTOMER Completed
02/26/2007 SUE REEVES REJECT SHELF Completed