Review Date Reviewer's Name Type of Review Description Status Comments
02/15/2007 ROBERT SHERRY PLUMBING-COMMERCIAL REVIEW Denied Second request. Provide information to show that the specified interceptor complies with the provisions of Appendix H, UPC 2003. See Section H 105.0, Construction Requirements. Note: the referenced cover, the Neenah R-1792 is not gasketed, as is required by Section H 105.2.3, UPC 2003.
02/21/2007 LEERAY HANLY BUILDING-COMMERCIAL REVIEW Approved

Final Status

Task End Date Reviewer's Name Type of Review Description
02/26/2007 FSANCHE1 OUT TO CUSTOMER Completed
02/26/2007 SUE REEVES REJECT SHELF Completed