Permit Review Detail
Review Status: Completed
Review Details: RESUBMITTAL
Permit Number - T06CM02576
Review Name: RESUBMITTAL
Review Status: Completed
Review Date | Reviewer's Name | Type of Review | Description | Status | Comments |
---|---|---|---|---|---|
01/08/2007 | ROBERT SHERRY | PLUMBING-COMMERCIAL | REVIEW | Denied | 1. The minimum available water pressure is to be used for the calculations, not the maximum water pressure. Confirm that the developed length of piping used in the calculations is the distance from the water meter to the most distant outlet. Reference Sections 610.4, 610.5, 610.6, 610.7, 610.8, and 610.9, UPC 2003. 2. Provide a vent for the grease interceptor. Reference Section 1009.4, UPC 2003. 3. Provide information to show that the specified interceptor complies with the provisions of Appendix H, UPC 2003. |
01/17/2007 | LINDA BUCZYNSKI | ELECTRICAL-COMMERCIAL | REVIEW | Approved | |
12/27/2006 | LEERAY HANLY | BUILDING-COMMERCIAL | REVIEW | Denied | PREVIOUS CORRECTION REQUESTS HAVE NOT BEEN ADDRESSED. 1) PROVIDE CORRECT CODE ANALYSIS FOR BUILDING WITH MIXED OCCUPANCIES. IF YOU ASSUME A2 OCC AS MOST RESTRICTIVE AND ADD SPRINKLER AND FRONTAGE INCREASES THEN YOU MAY USE NON SEPERATED USE. 2) PLEASE DO NOT SHOW EXISTING DEMISING WALLS AS 1 HOUR UNLESS CONTRACTOR INTENDS TO DO THE WORK REQUIRED TO MAKE THEM 1 HOUR CONSTRUCTION. 3) PROVIDE COMPLETE DETAILS FOR HOOD CONNECTIONS INCLUDING ALL STRUCTURAL ANALYSIS. |
Final Status
Task End Date | Reviewer's Name | Type of Review | Description |
---|---|---|---|
02/02/2007 | DELMA ROBEY | APPROVAL SHELF | Completed |
02/02/2007 | DELMA ROBEY | OUT TO CUSTOMER | Completed |
02/02/2007 | GERARDO BONILLA | REJECT SHELF | Completed |