Microfiche records prior to 2006 have not been completely digitized and may not be available yet on PRO. If you can not find what you are looking for please submit a records request.

Permit Number: T06CM02576
Parcel: 14118001H

Review Status: Completed

Review Details: RESUBMITTAL

Permit Number - T06CM02576
Review Name: RESUBMITTAL
Review Status: Completed
Review Date Reviewer's Name Type of Review Description Status Comments
01/08/2007 ROBERT SHERRY PLUMBING-COMMERCIAL REVIEW Denied 1. The minimum available water pressure is to be used for the calculations, not the maximum water pressure. Confirm that the developed length of piping used in the calculations is the distance from the water meter to the most distant outlet. Reference Sections 610.4, 610.5, 610.6, 610.7, 610.8, and 610.9, UPC 2003.
2. Provide a vent for the grease interceptor. Reference Section 1009.4, UPC 2003.
3. Provide information to show that the specified interceptor complies with the provisions of Appendix H, UPC 2003.
01/17/2007 LINDA BUCZYNSKI ELECTRICAL-COMMERCIAL REVIEW Approved
12/27/2006 LEERAY HANLY BUILDING-COMMERCIAL REVIEW Denied PREVIOUS CORRECTION REQUESTS HAVE NOT BEEN ADDRESSED.

1) PROVIDE CORRECT CODE ANALYSIS FOR BUILDING WITH MIXED OCCUPANCIES. IF YOU ASSUME A2 OCC AS MOST RESTRICTIVE AND ADD SPRINKLER AND FRONTAGE INCREASES THEN YOU MAY USE NON SEPERATED USE.

2) PLEASE DO NOT SHOW EXISTING DEMISING WALLS AS 1 HOUR UNLESS CONTRACTOR INTENDS TO DO THE WORK REQUIRED TO MAKE THEM 1 HOUR CONSTRUCTION.

3) PROVIDE COMPLETE DETAILS FOR HOOD CONNECTIONS INCLUDING ALL STRUCTURAL ANALYSIS.

Final Status

Task End Date Reviewer's Name Type of Review Description
02/02/2007 DELMA ROBEY APPROVAL SHELF Completed
02/02/2007 DELMA ROBEY OUT TO CUSTOMER Completed
02/02/2007 GERARDO BONILLA REJECT SHELF Completed