Permit Number: T06CM02576
Parcel: 14118001H

Review Status: Completed

Review Details: RESUBMITTAL

Permit Number - T06CM02576
Review Name: RESUBMITTAL
Review Status: Completed
Review Date Reviewer's Name Type of Review Description Status Comments
11/22/2006 DAVE MANN FIRE REVIEW Approved
11/22/2006 ROBERT SHERRY MECHANICAL-COMMERCIAL REVIEW Approved
11/22/2006 GERRY KOZIOL WWM REVIEW Approv-Cond
11/22/2006 ROBERT SHERRY PLUMBING-COMMERCIAL REVIEW Denied 1. The water calculations provided are incomplete; the developed length of piping is not included. The minimum available water pressure is to be used for the calculations, not the maximum water pressure. Reference Sections 610.4, 610.5, 610.6, 610.7, 610.8, and 610.9, UPC 2003.
2. Provide a cleanout for the floor sink located on the north side of the kitchen; it appears to have dropped off of the last submittal. Reference Section 707.4, UPC 2003.
3. The cleanouts provided for the hand sinks are too small to service the 3" drain piping to which they are connected. Each change of pipe size, for which a different size cleanout is required, must be provided with the properly sized cleanout. Reference Section 707.11, UPC 2003.
12/06/2006 LEERAY HANLY BUILDING-COMMERCIAL REVIEW Denied 1) PLEASE PROVIDE CORRECT CODE ANALYSIS FOR BUILDING AND MIXED OCCUPANCIES. CLARIFY HOW 1 HOUR OCCUPANCY SEPERATION WAS ARRIVED AT. TABLE 302.3.2 FO 2003 IBC REQUIRES 2 HOUR OCCUPANCY SEPERATION BETWEEN B AND M OCCUPANCIES. EXCEPTION TO 302.3.2 FOR 1 HOUR REDUCTION DOES NOT APPLY WHEN SPRINKLERS ARE USED FOR AREA INCREASES.

2) SHELL BUILDING PLAN DOES NOT INDICATE 1 HOUR DEMISING WALLS. PLEASE JUSTIFY "EXISTING" CONDITION AND PROVIDE FIRESTOP INFORMATION/DETAILS FOR MEMBRANE PENETRATIONS.

3) REFERERENCE CORRECTION NOTE DATED 10-20-06: PROVIDE COMPLETE DETAIL FOR HOOD CONNECTION. CLARIFY HOW NOTE ON ROOF SKETCH "EXISTING JOIST OK" WAS ARRIVED AT. CLARIFY HOW NOTE "(4) WOOD JOIST FOR SUPPORT HOOD" WAS ARRIVED AT. DETAIL CONNECTION OF "HANGING ANGLE DETAIL" TO HOOD AND TO STRUCTURAL FRAME. PLEASE PROVIDE STRUCTURAL CALCULATIONS FOR DEAD LOADS, LIVE LOADS, BENDING MOMENTS, ETC. FOR HOOD AND BLOWERS AS RELATED TO EXISTING STRUCTURE.
12/10/2006 LINDA BUCZYNSKI ELECTRICAL-COMMERCIAL REVIEW Denied Provide set of previously approved plans. This is a requirement for any re-submittal. Electrical Plans Examiner held plans from Nov. 29 until Dec 1 in order to allow Applicant, Jerry Curtis, to locate stamped/signed/approved plans. Per telephone conversation, the plans were held until Friday, December 1.
12/11/2006 TERRY STEVENS ZONING REVIEW Approved
12/20/2006 PAUL MACHADO ENGINEERING REVIEW Approved

Final Status

Task End Date Reviewer's Name Type of Review Description
12/26/2006 DELMA ROBEY OUT TO CUSTOMER Completed
12/26/2006 SUE REEVES REJECT SHELF Completed