Microfiche records prior to 2006 have not been completely digitized and may not be available yet on PRO. If you can not find what you are looking for please submit a records request.

Permit Number: T06CM02576
Parcel: 14118001H

Review Status: Completed

Review Details: COMMERCIAL TI

Permit Number - T06CM02576
Review Name: COMMERCIAL TI
Review Status: Completed
Review Date Reviewer's Name Type of Review Description Status Comments
07/10/2006 ROBERT SHERRY PLUMBING-COMMERCIAL REVIEW Denied 1. Revise the font size used on the drawings to a minimum of 1/8-inch (all upper case). Reference Section 302.3, Uniform Administrative Code, 1997.
2. Clarify how the 3-compartment sink and the floor sink relate to the grease trap. Provide a direct waste connection for the wash and rinse sections of the 3-compartment sink, with an indirect connection for the sanitizing compartment only. Only the directly connected sink compartments are to be connected to the grease trap. Reference Sections 103.2.3, 801.2.3, and 1014.1, UPC 2003.
3. Provide calculations showing how the water supply piping has been sized. Reference Sections 610.4 and 610.5, UPC 2003.
4. Provide upper terminal cleanouts on horizontal drainage pipes exceeding 5 feet in length (horizontal drain lines serving sinks and urinals require cleanouts regardless of length). Reference Section 707.4, UPC 2003.
5. Provide vent piping of sufficient size to comply with Section 904.1 and Table 7-5, UPC 2003 (e.g. a 3" trap (6 FU) or a total of 8 fixture units cannot be vented with a 1-1/2" vent).
6. Provide a vent to protect the grease trap from siphonage and back-pressure. Reference Section 1002.1, UPC 2003.
7. The flow control device for a grease trap shall be installed in a location that is readily accessible and visible. Reference Section 1014.3, UPC 2003.
07/10/2006 ROBERT SHERRY WATER REVIEW Denied 1. Provide information to show that Tucson Water will allow the placement of a reduced pressure zone backflow assembly inside of a building. Reference Section 27-76, COT Ordinance 9976, http://www.tucsonaz.gov/water/docs/backflow-ord.pdf
07/10/2006 ROBERT SHERRY MECHANICAL-COMMERCIAL REVIEW Denied 1. Clarify the type of hood being installed - type I or type II? Reference Section 106.3.1, IMC 2003.
2. Revise the font size used on the drawings to a minimum of 1/8-inch (all upper case). Reference Section 302.3, Uniform Administrative Code, 1997.
3. Terminate condensate drains (i.e. RTU-1 and RTU-2) in accordance with Section 307.2.1, IMC 2003, as amended by the City of Tucson.
4. Provide information on the sequence of operation for the restroom exhaust to show that recirculation of the air from the restroom will not occur. Reference Section 403.2.1, IMC 2003.
5. Provide structural calculations and details to show that the Type I [Type II] hood is supported from the building structure in accordance with Section 507.6, IMC 2003.
6. Provide adequate make up air for the kitchen exhaust hood. If the roof top air-conditioning units are supplying make up air for the kitchen hood, they shall be electrically interlocked to the exhaust fans. Reference Section 508.1, IMC 2003.
7. Provide information to show that the make up air for the kitchen hood complies with Section 508.1.1, IMC 2003.
07/11/2006 MARTIN BROWN FIRE REVIEW Approved
07/19/2006 LINDA BUCZYNSKI ELECTRICAL-COMMERCIAL REVIEW Denied TRANSMIT ORIGINAL DRAWINGS WITH NEXT SUBMITTAL.

PLEASE CALL AT 791-5550 X1106 OR EMAIL AT Linda.Buczynski@tucsonaz.gov
IF YOU CARE TO DISCUSS.

1. Please specify the grounding for the telephone system. Reference NEC 800.40.
2. Revise the font size used to a minimum of 1/8 inch (all upper case). Reference Section 302.3, Uniform Administrative Code, 1997.
3. Please remove the redundant GND in Conduit Run 4 on the line side of the service disconnect. Sheet E-1 Service Riser Diagram. Reference NEC 250.24 (B).
4. Provide service load calculations.
5. Provide sizes for existing equipment on the Service Riser Diagram, such as the Service Entrance Conductors, rating of CT can and gutter.
6. Obtain Tucson Electric Power Company Available Fault Current from its 2006 Electric Service Requirements, SR-510. For Example, 120/208V services powered from pad-mounted transformers have AFC of 55,600A for services ranging from 600A through 1000A.
7. Provide fault calculations for New Panel A.
8. Provide cut sheets for Fixture C and for the awning lighting fixtures.
9. Exterior lighting shall comply with the requirements of the Tucson Lighting Code, http://www.tucsonaz.gov/dsd/Codes___Ordinances/Tucson_Lighting_Code.pdf.
08/02/2006 GERRY KOZIOL WWM REVIEW Approved
08/09/2006 CHRISTY FOREMAN BUILDING-COMMERCIAL REVIEW Denied CITY OF TUCSON DEVELOPMENT SERVICES
STRUCTURAL REVIEW COMMENTS

DATE: 8/14/06
ACTIVITY NUMBER: T06CM02576
PROJECT NAME: Papa John's
PROJECT ADDRESS: 8270 S. Houghton Rd. #110
ARCHITECT / ENGINEER: Bayus Evola Architect
PROJECT REVIEWER: Christy Foreman


TRANSMIT ORIGINAL DRAWINGS WITH NEXT SUBMITTAL.

PLEASE CALL AT 791-5550 X1108 OR EMAIL AT CFOREMA1@TUCSONAZ.GOV IF YOU CARE TO DISCUSS.

1) Clarify actual sq. footage and occupancies of exiting building to justify non-separated use / most restrictive use.
2) Specify north on site plan and floor plan.
3) Span of joist does not appear to match shell building.
4) Provide specification on existing truss clarifying it can carry point loads.
5) Provide complete detail for hanging connection for hood to structural frame. Provide roof framing with location of fan and hood in reference to layout of pizza oven.
6) Provide drinking fountain per section 2902.1, 2003 IBC - provide spout heights and water flow ANSI A117.1 2003 - 602.4 and 602.6.
7) Clarify restroom is fully accessible. Accessible path is not allowed to pass through the kitchen see IBC 2003 section 1104.3.
8) Clarify occupant load for "B" occupancy
08/14/2006 BETSY COTTLE COMMERCIAL IMPACT FEE COMMERCIAL IMPACT FEE PROCESSING Completed Approved Development Plan D05-0011

Final Status

Task End Date Reviewer's Name Type of Review Description
08/15/2006 DELMA ROBEY OUT TO CUSTOMER Completed
08/15/2006 SUE REEVES REJECT SHELF Completed