Review Date | Reviewer's Name | Type of Review | Description | Status | Comments |
---|---|---|---|---|---|
05/24/2006 | CHRISTY FOREMAN | BUILDING-COMMERCIAL | REVIEW | Denied | ) CLARIFY SEPERATED / NONSEPARATED USE. ACTUAL BLDG. SQ. FOOTAGE AND MOST RESTRICTIVE USE OF BLDG. PROVIDE CODE ANALYSIS DATA SHT. 2) JUSTIFY OCCUANT LOAD PER TABLE 1004.1.2 |
05/24/2006 | ROBERT SHERRY | MECHANICAL-COMMERCIAL | REVIEW | Approved | |
05/24/2006 | ROBERT SHERRY | PLUMBING-COMMERCIAL | REVIEW | Denied | Provide information to show how the outlet temperature of the hot water is to be limited to 110 degrees at the lavatory. Reference Section 804.3, IECC 2003. |
05/31/2006 | CAGUILA1 | WWM | REVIEW | Needs Review | |
05/31/2006 | CAGUILA1 | ELECTRICAL-COMMERCIAL | REVIEW | Needs Review |