Permit Review Detail
Review Status: Completed
Review Details: COMMERCIAL TI
Permit Number - T06CM02539
Review Name: COMMERCIAL TI
Review Status: Completed
| Review Date | Reviewer's Name | Type of Review | Description | Status | Comments |
|---|---|---|---|---|---|
| 04/28/2006 | PATRICIA GILBERT | ENGINEERING | REVIEW | Approved | |
| 05/01/2006 | MARTIN BROWN | FIRE | REVIEW | Approved | |
| 05/01/2006 | ROBERT SHERRY | MECHANICAL-COMMERCIAL | REVIEW | Denied | 1. Provide calculations demonstrating adequate ventilation. Reference Section 401.2, IMC 2003. |
| 05/01/2006 | LINDA BUCZYNSKI | ELECTRICAL-COMMERCIAL | REVIEW | Denied | T06CM02539 5/1/06 Document any electrical work associated with the relocated Water Heater, or state on the plans that there is no electrical work on this project. |
| 05/01/2006 | ROBERT SHERRY | WATER | REVIEW | Approved | |
| 05/01/2006 | CHRISTY FOREMAN | BUILDING-COMMERCIAL | REVIEW | Denied | 1) CLARIFY SEPERATED / NONSEPARATED USE. ACTUAL BLDG. SQ. FOOTAGE AND MOST RESTRICTIVE USE OF BLDG. 2) JUSTIFY OCCUANT LOAD PER TABLE 1004.1.2 3) DIMENSION WIDTH OF SPACE. 4) CLARIFY USE OF BACK ROOM. 5) PROVIDE CLEAR FLOOR SPACE ENVELOPES ON DRAWINGS FOR RESTROOM FACILITIES AND CLARIFY SUITE IS FULLY ACCESSIBLE PER 3409.3. |
| 05/01/2006 | ROBERT SHERRY | PLUMBING-COMMERCIAL | REVIEW | Denied | 1. Provide a detail of the water heater installation, including the excess pressure relief, expansion tank, and valves. Reference Sections 103.2.3, 605.5, and 608.3 UPC 2003. 2. If the specified water heater is not supplied with integral heat traps, provide heat traps on the supply and discharge piping. Reference Section 804.4, IECC 2003. 3. Provide information to show how the outlet temperature of the hot water is to be limited to 110 degrees at the lavatory. Reference Section 804.3, IECC 2003. |
| 05/02/2006 | MICHAEL ST. PAUL | ZONING | REVIEW | Approved | |
| 05/24/2006 | AKLAPPE1 | WWM | REVIEW | Needs Review |