Permit Number: T06CM02539
Parcel: 113100050

Review Status: Completed

Review Details: COMMERCIAL TI

Permit Number - T06CM02539
Review Name: COMMERCIAL TI
Review Status: Completed
Review Date Reviewer's Name Type of Review Description Status Comments
04/28/2006 PATRICIA GILBERT ENGINEERING REVIEW Approved
05/01/2006 MARTIN BROWN FIRE REVIEW Approved
05/01/2006 ROBERT SHERRY MECHANICAL-COMMERCIAL REVIEW Denied 1. Provide calculations demonstrating adequate ventilation. Reference Section 401.2, IMC 2003.
05/01/2006 LINDA BUCZYNSKI ELECTRICAL-COMMERCIAL REVIEW Denied T06CM02539 5/1/06

Document any electrical work associated with the relocated Water Heater, or state on the plans that there is no electrical work on this project.
05/01/2006 ROBERT SHERRY WATER REVIEW Approved
05/01/2006 CHRISTY FOREMAN BUILDING-COMMERCIAL REVIEW Denied 1) CLARIFY SEPERATED / NONSEPARATED USE. ACTUAL BLDG. SQ. FOOTAGE AND MOST RESTRICTIVE USE OF BLDG.
2) JUSTIFY OCCUANT LOAD PER TABLE 1004.1.2
3) DIMENSION WIDTH OF SPACE.
4) CLARIFY USE OF BACK ROOM.
5) PROVIDE CLEAR FLOOR SPACE ENVELOPES ON DRAWINGS FOR RESTROOM FACILITIES AND CLARIFY SUITE IS FULLY ACCESSIBLE PER 3409.3.
05/01/2006 ROBERT SHERRY PLUMBING-COMMERCIAL REVIEW Denied 1. Provide a detail of the water heater installation, including the excess pressure relief, expansion tank, and valves. Reference Sections 103.2.3, 605.5, and 608.3 UPC 2003.
2. If the specified water heater is not supplied with integral heat traps, provide heat traps on the supply and discharge piping. Reference Section 804.4, IECC 2003.
3. Provide information to show how the outlet temperature of the hot water is to be limited to 110 degrees at the lavatory. Reference Section 804.3, IECC 2003.
05/02/2006 MICHAEL ST. PAUL ZONING REVIEW Approved
05/24/2006 AKLAPPE1 WWM REVIEW Needs Review