Microfiche records prior to 2006 have not been completely digitized and may not be available yet on PRO. If you can not find what you are looking for please submit a records request.

Permit Number: T06CM02533
Parcel: 10321029Y

Review Status: Completed

Review Details: RESUBMITTAL

Permit Number - T06CM02533
Review Name: RESUBMITTAL
Review Status: Completed
Review Date Reviewer's Name Type of Review Description Status Comments
06/22/2007 LEERAY HANLY BUILDING-COMMERCIAL REVIEW Denied S1) SEAL AND SIGN ALL PAGES OF SUBMITTED DRAWINGS. SEE PREVIOUS COMMENT S1.

S2) A ONE HOUR FIREWALL IS REQUIRED ON THE PROPERTY LINE PER IBC SECTIONS 406 AND 704 AND TABLES 601 AND 602. SEE PREVIOUS COMMENT S2.

S3) OBTAIN APPROVAL FROM BUILDING OFFICIAL FOR DEFERRED SUBMITTAL ITEMS OR SUBMIT PREVIOUSLY REQUESTED INFORMATION. SEE PREVIOUS COMMENT S9.

S4) PROVIDE SPECIAL INSPECTION PROGRAM. SPECIAL INSPECTION PROGRAMS ARE NOT PART OF A DEFERRED SUBMITTAL. SEE PREVIOUS COMMENT S10.

Final Status

Task End Date Reviewer's Name Type of Review Description
06/29/2007 GERARDO BONILLA OUT TO CUSTOMER Completed
06/29/2007 GERARDO BONILLA REJECT SHELF Completed