Microfiche records prior to 2006 have not been completely digitized and may not be available yet on PRO. If you cannot find what you are looking for please submit a records request.

Permit Number: T06CM02521
Parcel: 141153570

Review Status: Completed

Review Details: COMMERCIAL TI

Permit Number - T06CM02521
Review Name: COMMERCIAL TI
Review Status: Completed
Review Date Reviewer's Name Type of Review Description Status Comments
04/27/2006 PATRICIA GILBERT ENGINEERING REVIEW Approved
04/28/2006 HEATHER THRALL ZONING REVIEW Approved
04/28/2006 RAUL PALMA BUILDING-COMMERCIAL REVIEW Approved
05/01/2006 ROBERT SHERRY MECHANICAL-COMMERCIAL REVIEW Denied 1. Revise the utside air calculations to reflect the actual space usage and to correct the arithmetic.
2. Any new flexible duct shall have a minimum of R-5 insulation.
05/01/2006 ROBERT SHERRY PLUMBING-COMMERCIAL REVIEW Denied 1. If the specified water heater is not supplied with integral heat traps, provide heat traps on the supply and discharge piping. Reference Section 804.4, IECC 2003.
2. Provide information to show how the outlet temperature of the hot water is to be limited to 110 degrees at the lavatory. Reference Section 804.3, IECC 2003.
3. Show the basis for sizing the water piping.
4. Clarify the piping to the water heater as shown on the water riser diagrm.
05/01/2006 ROBERT SHERRY WATER REVIEW Approved
05/01/2006 MARTIN BROWN FIRE REVIEW Approved
05/02/2006 LINDA BUCZYNSKI ELECTRICAL-COMMERCIAL REVIEW Denied T06CM02521 5/2/06

1. Load tabulations for Phases A, B, and C appear to be 15632, 14434, and 15152 VA, respectively, not 13874, 13034, 13752.
2. Total VA and A appear to be 14149 VA, and 136.5A, not 44379VA and 123.2.
05/09/2006 GERRY KOZIOL WWM REVIEW Approved