Review Date Reviewer's Name Type of Review Description Status Comments
05/08/2006 LINDA BUCZYNSKI ELECTRICAL-COMMERCIAL REVIEW Denied T06CM02505 5/8/06

1. Provide panel and circuit number for all new electrical loads. THIS COMMENT WAS MADE ON THE FIRST REVIEW. There are 7 Quad receptacles 20A and one duplex, on Backboard, without panel/circuit.
2. Determine final layout for lighting fixtures, and plot it on the plans. THIS COMMENT WAS MADE ON THE FIRST REVIEW.
3. Clarify whether fixtures are existing or new. THIS COMMENT WAS MADE ON THE FIRST REVIEW.
4. Provide a lighting fixture schedule for any and all new fixtures. THIS COMMENT WAS MADE ON THE FIRST REVIEW.