Review Date Reviewer's Name Type of Review Description Status Comments
04/27/2006 LINDA BUCZYNSKI ELECTRICAL-COMMERCIAL REVIEW Denied T06CM02505 4/27/06

1. Provide panel and circuit number for all new electrical loads.
2. Provide panel schedule and load calculations.
3. Determine final layout for lighting fixtures, and plot it on the plans.
4. Clarify whether fixtures are existing or new.
5. Provide a lighting fixture schedule for any and all new fixtures.
04/28/2006 MARTIN BROWN FIRE REVIEW Approved
04/28/2006 RAUL PALMA BUILDING-COMMERCIAL REVIEW Approved
05/01/2006 ROBERT SHERRY MECHANICAL-COMMERCIAL REVIEW Passed
05/01/2006 ROBERT SHERRY PLUMBING-COMMERCIAL REVIEW Passed
05/01/2006 ROBERT SHERRY WATER REVIEW Approved
05/01/2006 HEATHER THRALL ZONING REVIEW Approved
05/01/2006 SUZANNE BOHNET ENGINEERING REVIEW Approved
05/08/2006 DROBEY1 WWM REVIEW Passed