Permit Review Detail
Review Status: Completed
Review Details: COMMERCIAL TI
Permit Number - T06CM02505
Review Name: COMMERCIAL TI
Review Status: Completed
Review Date | Reviewer's Name | Type of Review | Description | Status | Comments |
---|---|---|---|---|---|
04/27/2006 | LINDA BUCZYNSKI | ELECTRICAL-COMMERCIAL | REVIEW | Denied | T06CM02505 4/27/06 1. Provide panel and circuit number for all new electrical loads. 2. Provide panel schedule and load calculations. 3. Determine final layout for lighting fixtures, and plot it on the plans. 4. Clarify whether fixtures are existing or new. 5. Provide a lighting fixture schedule for any and all new fixtures. |
04/28/2006 | MARTIN BROWN | FIRE | REVIEW | Approved | |
04/28/2006 | RAUL PALMA | BUILDING-COMMERCIAL | REVIEW | Approved | |
05/01/2006 | ROBERT SHERRY | MECHANICAL-COMMERCIAL | REVIEW | Passed | |
05/01/2006 | ROBERT SHERRY | PLUMBING-COMMERCIAL | REVIEW | Passed | |
05/01/2006 | ROBERT SHERRY | WATER | REVIEW | Approved | |
05/01/2006 | HEATHER THRALL | ZONING | REVIEW | Approved | |
05/01/2006 | SUZANNE BOHNET | ENGINEERING | REVIEW | Approved | |
05/08/2006 | DROBEY1 | WWM | REVIEW | Passed |