Permit Number: T06CM02479
Parcel: 105102410

Review Status: Completed

Review Details: RESUBMITTAL

Permit Number - T06CM02479
Review Name: RESUBMITTAL
Review Status: Completed
Review Date Reviewer's Name Type of Review Description Status Comments
05/16/2006 LINDA BUCZYNSKI ELECTRICAL-COMMERCIAL REVIEW Denied T06CM02479 5/16/06

1. Sheet E1.1 missing.
2. Carry out fault calculations to sub panel, which is only rated for 10,000A.
3. Service is called "OVERHEAD" on Single Line Diagram Sheet E1.3. It is, however, drawn as an underground service, and furthermore, the City of Tucson does not typically allow new overhead services. Reference Section 108 City Amendments to the 1997 Uniform Administrative Code.
4. New Sub Panel is called Panel A on sheet E0.1, but is called Panel C on Sheet E1.3. Please clarify.