Review Details: RESUBMITTAL
Permit Number - T06CM02479
Review Name: RESUBMITTAL
Review Status: Completed
| Review Date | Reviewer's Name | Type of Review | Description | Status | Comments |
|---|---|---|---|---|---|
| 05/16/2006 | LINDA BUCZYNSKI | ELECTRICAL-COMMERCIAL | REVIEW | Denied | T06CM02479 5/16/06 1. Sheet E1.1 missing. 2. Carry out fault calculations to sub panel, which is only rated for 10,000A. 3. Service is called "OVERHEAD" on Single Line Diagram Sheet E1.3. It is, however, drawn as an underground service, and furthermore, the City of Tucson does not typically allow new overhead services. Reference Section 108 City Amendments to the 1997 Uniform Administrative Code. 4. New Sub Panel is called Panel A on sheet E0.1, but is called Panel C on Sheet E1.3. Please clarify. |