Permit Number: T06CM02479
Parcel: 105102410

Review Status: Completed

Review Details: OTHER

Permit Number - T06CM02479
Review Name: OTHER
Review Status: Completed
Review Date Reviewer's Name Type of Review Description Status Comments
05/11/2006 LINDA BUCZYNSKI ELECTRICAL-COMMERCIAL REVIEW Denied t06cm02479 5/10/06

INCOMPLETE REVIEW. SHEET E1.1 MISSING FROM CURRENT SET.

1. Show location of new panels, and provide fault calculations for available fault current at both panels. Panels shall be installed within their fault current rating.
2. Show all existing electrical services to the entire building. Demonstrate compliance with NEC 230.2.

5/10/06 Satisfy Comments #1 and #2 above.