Permit Number - T06CM02479
Review Name: OTHER
Review Status: Completed
| Review Date | Reviewer's Name | Type of Review | Description | Status | Comments |
|---|---|---|---|---|---|
| 05/11/2006 | LINDA BUCZYNSKI | ELECTRICAL-COMMERCIAL | REVIEW | Denied | t06cm02479 5/10/06 INCOMPLETE REVIEW. SHEET E1.1 MISSING FROM CURRENT SET. 1. Show location of new panels, and provide fault calculations for available fault current at both panels. Panels shall be installed within their fault current rating. 2. Show all existing electrical services to the entire building. Demonstrate compliance with NEC 230.2. 5/10/06 Satisfy Comments #1 and #2 above. |