Permit Number: T06CM02479
Parcel: 105102410

Review Status: Completed

Review Details: COMMERCIAL TI

Permit Number - T06CM02479
Review Name: COMMERCIAL TI
Review Status: Completed
Review Date Reviewer's Name Type of Review Description Status Comments
04/26/2006 MICHAEL ST. PAUL ZONING REVIEW Approved
04/26/2006 SUZANNE BOHNET ENGINEERING REVIEW Approved
04/26/2006 CHRISTY FOREMAN BUILDING-COMMERCIAL REVIEW Approved
04/27/2006 GERRY KOZIOL WWM REVIEW Passed
04/27/2006 LINDA BUCZYNSKI ELECTRICAL-COMMERCIAL REVIEW Denied T06CM02479 4/27/06

1. Ckt A-2 powers lighting according to the Lighting Plan. On the panel schedule it powers an existing receptacle.
2. Lighting circuits are not clearly drawn. Clarify which is the actual branch circuit run, the solid or the dashed. Some fixtures do not appear to have a circuit.
04/27/2006 MARTIN BROWN FIRE REVIEW Approved
05/01/2006 ROBERT SHERRY WATER REVIEW Approved
05/01/2006 ROBERT SHERRY PLUMBING-COMMERCIAL REVIEW Approved
05/10/2006 ROBERT SHERRY MECHANICAL-COMMERCIAL REVIEW Approved Show the size, route, and termination of the condensate drain for the RTU.