Review Status: Completed
Review Details: COMMERCIAL TI
Permit Number - T06CM02479
Review Name: COMMERCIAL TI
Review Status: Completed
Review Date | Reviewer's Name | Type of Review | Description | Status | Comments |
---|---|---|---|---|---|
04/26/2006 | MICHAEL ST. PAUL | ZONING | REVIEW | Approved | |
04/26/2006 | SUZANNE BOHNET | ENGINEERING | REVIEW | Approved | |
04/26/2006 | CHRISTY FOREMAN | BUILDING-COMMERCIAL | REVIEW | Approved | |
04/27/2006 | GERRY KOZIOL | WWM | REVIEW | Passed | |
04/27/2006 | LINDA BUCZYNSKI | ELECTRICAL-COMMERCIAL | REVIEW | Denied | T06CM02479 4/27/06 1. Ckt A-2 powers lighting according to the Lighting Plan. On the panel schedule it powers an existing receptacle. 2. Lighting circuits are not clearly drawn. Clarify which is the actual branch circuit run, the solid or the dashed. Some fixtures do not appear to have a circuit. |
04/27/2006 | MARTIN BROWN | FIRE | REVIEW | Approved | |
05/01/2006 | ROBERT SHERRY | WATER | REVIEW | Approved | |
05/01/2006 | ROBERT SHERRY | PLUMBING-COMMERCIAL | REVIEW | Approved | |
05/10/2006 | ROBERT SHERRY | MECHANICAL-COMMERCIAL | REVIEW | Approved | Show the size, route, and termination of the condensate drain for the RTU. |