Microfiche records prior to 2006 have not been completely digitized and may not be available yet on PRO. If you cannot find what you are looking for please submit a records request.

PRO is currently experiencing an outage. Some documents and records may not be available on PRO momentarily. We apologize for the inconvenience and are working to restore full access.

Permit Number: T06CM02458
Parcel: 105102410

Review Status: Completed

Review Details: COMMERCIAL TI

Permit Number - T06CM02458
Review Name: COMMERCIAL TI
Review Status: Completed
Review Date Reviewer's Name Type of Review Description Status Comments
04/26/2006 MICHAEL ST. PAUL ZONING REVIEW Approved
04/26/2006 SUZANNE BOHNET ENGINEERING REVIEW Approved
04/26/2006 LINDA BUCZYNSKI ELECTRICAL-COMMERCIAL REVIEW Denied T06CM02458 4/26/06

1. Ckt A-2 powers lighting according to the Lighting Plan. On the panel schedule it powers an existing receptacle.
2. Lighting circuits are not clearly drawn. Clarify which is the actual branch circuit run, the solid or the dashed. Some fixtures do not appear to have a circuit.
3. New Electrical Service and its new sub panels, including the New RTU, is not a part of the Shell occupancy. This all would appear to need a separate permit.
4. Please note that TEP publishes Available Fault Current for 400A 208V service as being 27,800A. 20,000A bracing not sufficient, or justify otherwise.
5. Can not evaluate whether a second electrical service may be permitted to this building. Reference NEC 230.2.
04/27/2006 GERRY KOZIOL WWM REVIEW Needs Review
04/27/2006 CHRISTY FOREMAN BUILDING-COMMERCIAL REVIEW Approved
04/27/2006 MARTIN BROWN FIRE REVIEW Approved
05/01/2006 ROBERT SHERRY WATER REVIEW Approved
05/01/2006 ROBERT SHERRY PLUMBING-COMMERCIAL REVIEW Passed
05/10/2006 ROBERT SHERRY MECHANICAL-COMMERCIAL REVIEW Approved Show the size, route, and termination of the condensate drain for the RTUs.