Permit Review Detail
Review Status: Completed
Review Details: COMMERCIAL TI
Permit Number - T06CM02456
Review Name: COMMERCIAL TI
Review Status: Completed
| Review Date | Reviewer's Name | Type of Review | Description | Status | Comments |
|---|---|---|---|---|---|
| 04/26/2006 | CHRISTY FOREMAN | BUILDING-COMMERCIAL | REVIEW | Denied | 1) PROVIDE STRUCTURAL DETAIL ON DRAWINGS WITH A MINIMUM OF 1/8" TEXT FOR RECORD PURPOSES. 2) DETAIL MISSING VERTICAL SIDE PLATES ON DRAWING 201 ALSO WIDTH OF LINTEL NEEDS TO BE SPECIFIED ON DETAIL. |
| 05/01/2006 | ROBERT SHERRY | MECHANICAL-COMMERCIAL | REVIEW | Denied | 1. The minimum font size is 1/8', all upper case. |
| 05/01/2006 | ROBERT SHERRY | PLUMBING-COMMERCIAL | REVIEW | Denied | 1. The minimum font size is 1/8", all upper case. 2. Provide information for all loads connected to the gas meter to show that the piping is correctly sized. |
| 05/01/2006 | ROBERT SHERRY | WATER | REVIEW | Approved | |
| 05/01/2006 | HEATHER THRALL | ZONING | REVIEW | Approved | |
| 05/01/2006 | SUZANNE BOHNET | ENGINEERING | REVIEW | Approved | |
| 05/01/2006 | MARTIN BROWN | FIRE | REVIEW | Approved | |
| 05/05/2006 | AKLAPPE1 | WWM | REVIEW | Needs Review | |
| 05/05/2006 | AKLAPPE1 | ELECTRICAL-COMMERCIAL | REVIEW | Needs Review |